. Analog Input Module Definition.
3) Edit each point:
Position the cursor on a Point definition and choose Edit
from the Module Definition dialog box to define a name
and description for each I/O point. In the Analog Input
Point dialog, enter a tag name (up to 12 characters) and a
description (u
p to 40 characters). The tag names are used
in the application program to represent the value of the
analog input in your control algorithms and interlocks.
Figure
16
. Defining an Analog Input Point.
Programming
Inputs are referenced in the application program through the
tag names defined in the I/O Configuration Editor. The
analog inputs will range in value from 0 to 4095 over the
voltage range configured for the analog input module. Most