Monitored Digital Input Modules
, Type F (T7411F, T7418F)
PD
-
7027
Mar
-
06
13
With the line monitor device installed, the input voltage, V
in
,
has four possible states as represented in Table
1
. When the
input module reads the input, the reference voltage, V
ref
,
is
set to the values shown in Table
1
to detect the state of the
input.
Table
1
. Input States and Reference Voltage Thresholds.
V
ref
Threshold
Voltage
V
in
with Line
Monitor
V
in
without
Line Monitor
Stuck
-
on Test
32 Vdc
24 Vdc
Wire Open
Switch Open
Open Circuit
20 Vdc
16 Vdc
Switch Open
NA
On/Off
12 Vdc
8 Vdc
Switch Closed
NA
Short Circuit
4 Vdc
0 Vdc
Wire Short
Switch Closed
Stuck
-
Off Test
-
5 Vdc
The actual voltage levels for the T7418
F are half that shown
in Table
1
, e.g. the On/Off threshold is 6 Vdc and a line
monitored Switch Open is 8 Vdc. However, when configuring
the input module voltage thresholds, the settings should be as
shown in Table
1
, i.e. 4 Vdc, 12 Vdc and 20 Vdc. The input
module will automatically halve these setting values for the
input module reference voltages.
Keying
The I/O chassis can be physically keyed to prevent accidental
damage caused by inserting a mo
dule into a slot wired for a
different module type. Figure
8
illustrates how the slot keys
are installed on the I/O chassis slot field wiring connectors.
The slot key positions for the monitored digital input module
are listed in Table
2
.
Note: