Rockwell-automation T8451 Trusted TMR 24V dc Digital Output Module - 4 Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 32
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
Trusted
TM
Module T8451
Issue 12 Apr 10 PD-T8451 17
2.5. Trusted
TM
Module Polarisation/keying.
All Trusted
T
M
Modules have been Keyed to prevent insertion into the wrong position within a chassis.
The polarisation comprises two parts. The module and the associated field cable.
E
ach module type has been keyed during manufacture. The organisation responsible for the
integration of the Trusted
TM
system must key the cable by removing the keying pieces from the cable
so that they correspond with the bungs fitted to the associated module prior to fitting.
1
12
Cable Exit
Release button
Polarising/Keying
Pins.
(Remove using
side cutters where
identified below)
Trusted Cable
hood
Smart
Swap
Connector
if Fitted
Figure 5 Module polarisation
For Cables with Companion slot installations both keying strips must be polarised.
For This Module (T8451) remove keying pins 1,5,6
Vista de pagina 16