Rockwell-automation T8451 Trusted TMR 24V dc Digital Output Module - 4 Manual de usuario Pagina 19

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 32
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 18
Trusted
TM
Module T8451
Issue 12 Apr 10 PD-T8451 19
OEM Parameter Description Notes
TICS_CHASSIS The number of the
Trusted
TM
Chassis where
the primary I/O module is
installed
The Trusted
TM
Controller Chassis is 1, and
Trusted
TM
Expander Chassis are 2 to 15
TICS_SLOT The slot number in the
chassis where the primary
I/O module is installed
The I/O module slots in the Trusted
T
M
Controller chassis are numbered from 1 to 8.
The I/O Module slots in the Trusted
TM
Expander Chassis are numbered from 1 to 12
Table 4 OEM Parameters
3.2.1. Rack 1: DO
This board provides the connection to the logical output control signal for each of the field outputs.
Channel Description
1 Field output channel 1 logical state
2 Field output channel 2 logical state
40 Field output channel 40 logical state
Table 5 Rack 1: DO descriptions
The user application should set the output control signal to true (logic1) to turn ON or energise an
output, and false (logic ‘0’) to turn OFF or de-energise an output.
3.2.2. Rack 2: STATE
This board provides the majority voted numerical output state. This indicates the operational status of
the output channel and associated field connection.
Channel Description
1 Field output channel 1 state
2 Field output channel 2 state
40 Field output channel 40 state
Table 6 Rack 2: STATE descriptions