Rockwell-automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 20
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
XM Dynamic Measurement Module 17
Publication
ICM-IN002A-EN-P - March 2009
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication
1770-4.1.
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM
from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM
at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM
at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4:
±4 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
±2 kV at 5 kHz on communications ports
Surge Transient Immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth
(CM) on power ports
±1 kV line-line (DM) and ±2 kV line-earth
(CM) on signal ports
±2 kV line-earth (CM) on shielded ports
±2 kV line-earth (CM) on communications
ports
Conducted RF Immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz
Environmental Specifications
Attribute Value