Rockwell-automation 1732E-IB16M12SOEDR EtherNet/IP ArmorBlock supporti Manual de usuario Pagina 83

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 132
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 82
Publication 1732E-UM002A-EN-P - March 2010
ArmorBlock 2 Port Ethernet Module Specifications 75
EFT/B immunity IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±3 kV @ 5 kHz on signal ports
±3 kV @ 5 kHz on communications ports
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on communications ports
Conducted RF
immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certification (when
product is marked)
(1)
Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E322657.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
EtherNet/IP ODVA conformance tested to Ethernet/IP specifications.
(1)
See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other
certification details.
Environmental Specifications
Attribute Value