16 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Publication 1732E-IN005B-EN-E - September 2012
Indicator Status for the Modules
Indicator Status Description
Module status Off No power applied to the device.
Flashing red/green The module is performing POST (Power-On Self Test),
which completes within 30 s.
Green Device operating normally.
Flashing red Module has experienced a recoverable fault. Possible
minor faults include the following:
• IP Address switches do not match configuration in use.
• The device has completed a reset to factory default
request due to the switches being set to 888 at power
up, and a power cycle is required.
• The device is performing a firmware flash update.
• Channel fault
• No auxiliary power
Red Unrecoverable fault – may require device replacement.
Network status Off The device is not initialized or the module does not have an
IP address.
Flashing green The device has no CIP connections. The device has an IP
address, but no CIP connections are established.
Green Device is online, has an IP address. CIP connections are
established.
Flashing red One or more connections have timed out.
Red The module has detected that its IP address is
already in use.
Flashing red/green The module is performing a power-on self test (POST).
Network link
status
(Link 1/Link 2)
Off No link established.
Green Link established on indicated port at 100 Mbps.
Flashing green Link activity present on indicated port at 100 Mbps.
Yellow Link established on indicated port at 10 Mbps.
Flashing yellow Link activity present on indicated port at 10 Mbps.
Auxiliary
Power status
Off Auxiliary power off or not connected.
Green Auxiliary Power applied to device.
Comentarios a estos manuales