1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 19
Publication 1732E-IN005B-EN-E - September 2012
Thermocouple types Type Material Temperature
Range °C (°F)
Voltage
Range (mV)
B Pt /30% Rh vs. Pt/5% Rh 40…1820
(104…3308)
0…13.820
C W/5% Re vs. W/26% Re 0…2320
(32…4208)
0…37.107
E Ni/Cr vs. Cu/Ni -270…1000
(-454…1832)
-9.835…76.373
J Ni/Cr vs. Cu/Ni -210…1200
(-346…2192)
-8.095…69.553
K Ni/Cr vs. Ni/Al -270…1372
(-454…2501.6)
-6.458…54.886
N Ni/14.2%Cr/1.4%Si vs.
Ni/4.4%Si/0.1%Mg
-270…1300
(-454…2372)
-4.345…47.513
R Pt/13%Rh vs. Pt -50…1768
(-58…3214.4)
-0.226…21.101
S Pt/10%Rh vs. Pt -50…1768
(-58…3214.4)
-0.236…18.693
T Cu vs. Cu/Ni -270…400
(-454…752)
-6.258…20.872
CJC Terminal Chamber
recommended
Rockwell Automation 871A-TS4CJC-DM, 871A-TR4CJC-DM
Cold junction
compensation range
0…70 °C (32…158 °F) for 302 type thermistors
Cold junction
compensation modes
Average Selected, Channel Independent, and CJC Offset
(For more information, see the User Manual, publication 1732E-UM004
)
Thermistor types
supported
Thermometrics MF65F302V/W or DC95F302V/W
Input voltage range ±78.125 mV
0…78.125 mV
Accuracy 0.1% Full Scale @ 25 °C (77 °F)
Accuracy drift with
temperature
30 ppm % Full Scale /°C @ 25 °C (77 °F)
Calibration Factory calibrated. Calibration is also supported through RSLogix 5000.
Input Specifications – 1732E-IT4IM12R
Attributes Value