16 POINT I/O DeviceNet Adapter
Publication
1734-IN026A-EN-P - April 2005
Indicator Indication Probable Cause Take This Action
System
Power
Off Not active
Field power is OFF.
DC-DC converter
problem
Check adapter
configuration.
Turn field power
ON.
Contact
Customer
Support.
Green System power is ON.
DC-DC converter is
active (5V).
None
Field Power Off Not active
Field power is OFF.
Check adapter
configuration.
Turn field power
ON.
Green Power is ON with 24V present. None
43933
System power
Field power
Adapter status
Network status
Subnet status
Status indicators for 1734-ADNX adapters
Adapter
Status
Field
Power
DeviceNet
Status
1734-ADNX
Subnet
Status
System
Power