POINT I/O DeviceNet Adapter 17
Publication
1734-IN026A-EN-P - April 2005
Adapter
Status
Off No power is applied to device. Power the adapter.
Green Device is operating normally. None
Flashing
Green
Device needs to be
commissioned because
configuration is missing,
incomplete, or incorrect
Check configuration and
recommission the adapter.
Flashing
Red
Recoverable fault is present. Make sure the adapter does
not need a FLASH update.
Red Unrecoverable fault may require
device replacement.
Replace the adapter.
Flashing
Red/Green
Device is in self-test. Wait for self-test to finish.
Network
Status
Off Device is not online.
- Device is autobauding .
- Device has not completed
dup_MAC_id test.
- Device is not powered.
Check adapter status
indicator to determine if you
need more time to complete
the dup_MAC_id test or if
you need to power the
adapter.
Flashing
Green
Device is online but has no
connections in the established
state.
None
Green Device is online and has
connections in the established
state.
None
Flashing
Red
One or more I/O connections are
in timed-out states
Determine the cause of the
time-out. You may need to
increase the expected
packet rate.
Red Critical link failure -
communication device failed.
Device detected error that
prevents it from communicating
on the network.
Make sure the device is
using the correct MAC ID
and baudrate.
Indicator Indication Probable Cause Take This Action