Publication 1746-UM026A-EN-P - September 2003
Configuring the Module 4-5
d. The “Options” pull-down allows selection of the data format
(bits 4 to 6 of the channel configuration word):
Options:
1746-NO4 Data Format
Engineering Units
Scaled for PID
Proportional Counts
User-defined
e. “Latch Alarms” and “Reset Latched Alarms” check boxes allow
channel configuration word bits 14 and 15 to be configured.
f. The “Fault Options” pull-down allows channel configuration
fault options to be selected (bits 12 and 13 of the channel
configuration word).
Fault Options:
Reset Output
Hold Output
Preset Output
Refer to the remaining sections of this chapter for a full description of
the available configuration selections.