6-4 Module Diagnostics and Troubleshooting
Interpreting I/O Error Codes
I/O error codes appear in word S:6 of the SLC 500 processor status
file. The first two digits of the error code identify the slot (in
hexadecimal) experiencing the error. The last two digits identify the
I/O error code (in hexadecimal).
The error codes that apply to the 1746-NO8 module include (in
hexadecimal):
50 to 5E (I/O errors)
71 (watchdog error)
90 to 94 (I/O errors)
Refer to the SLC 500 Instruction Set Reference Manual, publication
1747-RM001 for a complete listing of error codes, probable causes,
and recovery information.