Publication 1746-UM026A-EN-P - September 2003
Configuring the Module 4-19
Ladder Program to
Configure Channel 0
]/[
I:1.8
1
OTHER
0000
MOV
MOVE
Source 20000
20000
Dest O:1.24
10000
<
<
CH0_PARAMETER2
MOV
MOVE
Source 5393
5393
Dest 0:1.8
4113
<
<
CH0_CONFIG
MOV
MOVE
Source 4000
4000
Dest O:1.16
5000
<
<
CH0_PARAMETER1CH0_CLAMPING_SET
The rung below configures Channel 0 for 0 to 21 mA, sets the clamping range from 4000 to 20000, and holds the output in its last state on a fault
condition.
Note: 5393 decimal = 0001 0101 0001 0001 binary.