108 Application Examples
Channel Configuration
Configure the RTD channel with the following setup:
200 Ω Platinum RTD
°F in whole degrees
Zero data word in the event of an open or short circuit
10 Hz input filter
2.0 mA excitation current
Channel Configuration Worksheet (With Settings Established for Channel 0)
Input Type Select
Data Format select
Broken Input Select
Temperature Units Select
Filter Frequency Select
Channel Enable
Excitation Current Select
Scaling Select
Not Used
Channel 0
Channel 1
Channel 2
Channel 3
1112131415
0
910 8 67450123
0
0
0
Bit Number
000100100010001