Publication 1746-UM008B-EN-P - December 2006
74 Channel Configuration, Data, and Status
The Channel Data Word Resolution for RTDs table shows the data
resolution provided by the 1746-NR4 for RTD input types using the
various data formats.
The Channel Data Word Resolution for 150 Ω Resistance Input table
and the Channel Data Word Resolution for 500 Ω, 1000 Ω, and 3000
Ω Resistance Inputs table shows the data resolution provided by the
1746-NR4 for resistance input types using the various data formats.
Channel Data Word Resolution for RTDs
RTD Input Type
Data Format (Bits 4 and 5)
(1)
Engineering Units x 1
Engineering Units
x 10
Scaled-for-PID
Proportional Counts
(Defaults)
°C °F °C °F °C °F °C °F
100 Ω Platinum 385 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0641 °C/step 0.1154 °F/step 0.0160 °C/step 0.0288 °F/step
200 Ω Platinum 385 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0641 °C/step 0.1154 °F/step 0.0160 °C/step 0.0288 °F/step
500 Ω Platinum 385 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0641 °C/step 0.1154 °F/step 0.0160 °C/step 0.0288 °F/step
1000 Ω Platinum 385 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0641 °C/step 0.1154 °F/step 0.0160 °C/step 0.0288 °F/step
100 Ω Platinum 3916 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0507 °C/step 0.0912 °F/step 0.0127 °C/step 0.0288 °F/step
200 Ω Platinum 3916 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0507 °C/step 0.0912 °F/step 0.0127 °C/step 0.0288 °F/step
500 Ω Platinum 3916 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0507 °C/step 0.0912 °F/step 0.0127 °C/step 0.0288 °F/step
1000 Ω Platinum 3916 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0507 °C/step 0.0912 °F/step 0.0127 °C/step 0.0288 °F/step
10 Ω Copper 426 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0220 °C/step 0.0396 °F/step 0.0051 °C/step 0.0099 °F/step
120 Ω Nickel 618
(2)
0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0220 °C/step 0.0396 °F/step 0.0051 °C/step 0.0099 °F/step
120 Ω Nickel 672 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0208 °C/step 0.0374 °F/step 0.0052 °C/step 0.0093 °F/step
604 Ω Nickel Iron 518 0.1 °C/step 0.1 °F/step 1 °C/step 1 °F/step 0.0183 °C/step 0.0330 °F/step 0.0046 °C/step 0.0082 °F/step
(1)
When ohms are selected, the temperature-units selection (bit 8) is ignored. Analog input data is the same for either °C or °F selection.
(2)
Actual value at 0 °C (32 °F) is 100Ω per DIN standard.
Channel Data Word Resolution for 150 Ω Resistance Input
Resistance Input Type
Data Format (Bits 4 and 5)
Engineering Units x 1 Engineering Units x 10 Scaled-for-PID
Proportional Counts
(Defaults)
Ohms Ohms Ohms Ohms
150 Ω 0.01 Ω / step 0.1 Ω / step 0.0092 Ω / step 0.0023 Ω / step
Vista de pagina 73