112 Application Examples
Channel Configuration
See completed worksheet in Channel Configuration Worksheet (With
Settings Established) on page 113.
Configuration setup for ambient RTD includes the following:
channel 0
604 Ω Nickel/Iron (518)
display temperature to tenths of a degree Celsius
zero data word in the event of an open or short circuit
60 Hz input filter to provide 60 Hz line noise rejection
use 2.0 mA excitation current for RTD
select module defined scaling
Configuration setup for bath RTD includes the following:
channel 1
200 Ω Platinum RTD (385)
display temperature to tenths of a degree Celsius
zero data word in the event of an open or short circuit
60 Hz input filter to provide 60 Hz line noise rejection
use 2.0 mA excitation current for RTD
select module defined scaling
Configuration setup for steam RTD includes the following:
channel 2
1000 Ω Platinum RTD (385)
display temperature to tenths of a degree Celsius
zero data word in the event of an open or short circuit
60 Hz input filter to provide 60 Hz line noise rejection
use 0.5 mA excitation current for RTD
select module defined scaling
Configuration setup for chilled H2O RTD the following:
channel 3
200 Ω Platinum RTD (385)
display temperature to tenths of a degree Celsius
zero data word in the event of an open or short circuit
60 Hz input filter to provide 60 Hz line noise rejection
use 2.0 mA excitation current for RTD
select module defined scaling