Publication 1756-IN602A-EN-P - November 2005Installation InstructionsControlLogix ControlNet Bridge ModuleCatalog Numbers 1756-CN2, 1756-CN2RInside .
10 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005For information about installing these products, refer to the
ControlLogix ControlNet Bridge Module 11Publication 1756-IN602A-EN-P - November 2005 Install the Module1. Align the circuit board with top and bot
12 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Connect the Module to the NetworkYou can connect the module to
ControlLogix ControlNet Bridge Module 13Publication 1756-IN602A-EN-P - November 2005Connect to the Network Using a TapFollow these steps to connec
14 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 20053. Apply power to the module and check module status. IMPORTAN
ControlLogix ControlNet Bridge Module 15Publication 1756-IN602A-EN-P - November 2005Use this flowchart as a guide.Turn the chassis power supply on
16 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Connect a Programming Terminal to the Network with 1786-CP Cab
ControlLogix ControlNet Bridge Module 17Publication 1756-IN602A-EN-P - November 2005• Use a 1770-KFC communication interface, a serial or parallel
18 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Remove the ModuleFollow these steps to remove the module:1. Pu
ControlLogix ControlNet Bridge Module 19Publication 1756-IN602A-EN-P - November 2005Install or Remove the Module Under PowerYou can install or rem
2 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Important User Information Solid state equipment has
20 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Module Status Indicator and DisplayThe Module Status Indicator
ControlLogix ControlNet Bridge Module 21Publication 1756-IN602A-EN-P - November 2005Red BPIC ERRHardware fault within the module.Replace the modul
22 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Green OK Normal operation. There is at least one connection to
ControlLogix ControlNet Bridge Module 23Publication 1756-IN602A-EN-P - November 2005ControlNet Channel Status IndicatorsThe ControlNet channel sta
24 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Flashing green/offTemporary errors None; unit will self-corre
ControlLogix ControlNet Bridge Module 25Publication 1756-IN602A-EN-P - November 2005Specifications ControlLogix ControlNet Bridge Mod
26 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Backplane current 970 mA @ 5.1 V 1.7 mA @ 24 VIsolation voltag
ControlLogix ControlNet Bridge Module 27Publication 1756-IN602A-EN-P - November 2005Radiated RF immunity IEC 61000-4-3: 10 V/m with 1 kHz sine-wav
28 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005CertificationsCertification ValueAgency certification (when pr
ControlLogix ControlNet Bridge Module 29Publication 1756-IN602A-EN-P - November 2005Additional Resources ControlLogix is a trademark of Rockwell A
ControlLogix ControlNet Bridge Module 3Publication 1756-IN602A-EN-P - November 2005European Hazardous Location ApprovalEuropean Zone 2 Certificati
30 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Notes:
ControlLogix ControlNet Bridge Module 31Publication 1756-IN602A-EN-P - November 2005
Publication 1756-IN602A-EN-P - November 2005 PN 957974-09Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.Rockwell
4 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005North American Hazardous Location ApprovalThe following informa
ControlLogix ControlNet Bridge Module 5Publication 1756-IN602A-EN-P - November 2005Environment and EnclosureATTENTIONThis equipment is intended fo
6 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Preventing Electrostatic DischargeFor additional information, r
ControlLogix ControlNet Bridge Module 7Publication 1756-IN602A-EN-P - November 2005Before You BeginBefore you install the module, make sure you:•
8 ControlLogix ControlNet Bridge Module Publication 1756-IN602A-EN-P - November 2005Identify Module FeaturesRefer to this figure to identify the ha
ControlLogix ControlNet Bridge Module 9Publication 1756-IN602A-EN-P - November 2005Set the Module’s Network Address SwitchesUse your fingers or a