ProcessLogix Pulse Input Module 3
Publication 1757-IN900A-US-P - February 2000
Installing the Module
Follow the procedure below to install the module.
Making Field Wiring Connections
Refer to the following pinout/wiring diagram to wire the module.
Figure 1 Pinouts and Wiring Example
ATTENTION
!
This input module permits the field-side input device (switch)
to be located on either the hot or neutral side of the source,
unless the module’s shorting bar has been installed. In this
case, the input device must be installed on the hot side of the
source.
This diagram illustrates how the eight transmitters will interface to the 36 Positions Terminal Block.
For instance, Transmitter 0 will be connected to Pins 1, 3 and 5 where:
Pin 1 is the Signal
Pin 3 is the Signal Common
Pin 5 is the Chassis Ground Shield Connection
The Output Channel 0 will connect to Pins 33 and 35 and Output Channel 1 will connect to Pins 34
and 36.