I–1UserManual1771–DB BasicModuleAllen-Bradley
Using This ManualChapter 11–2There are three different types of precautionary statements in this manual:Important, CAUTION and WARNING.Important: used
Operating FunctionsChapter 55–63This routine gets the current character in the 255 character, peripheral portinput buffer. It returns the decimal repr
Operating FunctionsChapter 55–64Example: u10 REM PERIPHERAL PORT INPUT USING CALL 35 u20 STRING 200,20 u30 DIM D(254) u40 CALL 35: POP X u50 IF X tu2
Operating FunctionsChapter 55–65Use this routine to retrieve the number of characters in the chosen buffer asits output argument. You must PUSH which
Operating FunctionsChapter 55–66This routine has one input argument and no output arguments. If no IDnumber is pushed prior to CALL 38, an error occur
Operating FunctionsChapter 55–67CALL 111 prints the complete buffer with addresses, front pointer and thenumber of characters in the buffer to the con
Operating FunctionsChapter 55–68Use this routine to set the following wall clock time functions:H = hours (0 to 23)M = minutes (0 to 59)S = seconds(0-
Operating FunctionsChapter 55–69CALL 43 returns the current date and time as a string. PUSH the numberof the string to receive the date/time (dd/mmm/y
Operating FunctionsChapter 55–70The time of day is available in numeric form by executing a CALL 46 andPOPing the three variables off of the argument
Operating FunctionsChapter 55–71CALL 52 returns the current date in a string (dd/mmm/yy). PUSH thenumber of the string to receive the date. You must a
Operating FunctionsChapter 55–72Two operators in the BASIC Module can manipulate STRINGS. Theseoperators are ASC() and CHR(). The ASC() operator retur
Chapter 2Introducing the BASIC ModuleThis chapter discusses the functions and features of the BASIC Module.When you finish reading this chapter, you s
Operating FunctionsChapter 55–73You can also use the ASC() operator to change individual characters in adefined string.Example:u5 STRING 1000,40 u10 $
Operating FunctionsChapter 55–74The CHR() operator converts a numeric expression to an ASCII character.Example:uPRINT CHR(65) ALike the ASC() operator
Operating FunctionsChapter 55–755.10.2.2 Cursor Positioning on an Industrial TerminalAllen-Bradley Industrial Terminal – Refer to the Industrial Termi
Operating FunctionsChapter 55–76It is important to note that since the carriage return character is the stringterminator, you cannot use it within a s
Operating FunctionsChapter 55–77Example program 1: uLIST 10 REM STRING ALLOCATION COMPUTATION KNOWING: 20 REM 1)# CHARACTERS IN LONGEST STRING 2)# OF
Operating FunctionsChapter 55–78Example program 2: uLIST 10 REM STRING ALLOCATION COMPUTATION KNOWING: 20 REM 1)# CHARACTERS IN LONGEST STRING 2) AMOU
Operating FunctionsChapter 55–79Example program 3: 10 REM STRING ALLOCATION COMPUTATION KNOWING: 20 REM 1) AMOUNT OF STRING MEMORY 2) #OF STRING VARI
Operating FunctionsChapter 55–805.10.3.1 String Repeat – CALL 60 This routine allows you to repeat a character and place it in a string. Youcan use th
Operating FunctionsChapter 55–815.10.3.2 String Append (Concatenation) – CALL 61This routine allows you to append one string to the end of another str
Operating FunctionsChapter 55–825.10.3.4 String to Number Conversion – CALL 63This routine converts the first decimal number found in the specified st
Introducing the BASIC ModuleChapter 22–2Figure 2.1BASIC Module Front EdgeYour module is a one-slot module with the following functions andfeatures:13
Operating FunctionsChapter 55–835.10.3.5 Find a String in a String – CALL 64This routine finds a string within a string. It locates the first occurren
Operating FunctionsChapter 55–845.10.3.6 Replace a String in a String – CALL 65This routine replaces a string within a string. Three arguments areexpe
Operating FunctionsChapter 55–855.10.3.7 Insert String in a String – CALL 66This routine inserts a string within another string. The call expects thre
Operating FunctionsChapter 55–865.10.3.8 Delete String from a String – CALL 67This routine deletes a string from within another string. The call expec
Operating FunctionsChapter 55–875.10.3.9 Determine Length of a String – CALL 68This routine determines the length of a string. One input argument isex
Operating FunctionsChapter 55–88This routine shifts program execution from a running ROM program to thebeginning of the RAM program. No arguments are
Operating FunctionsChapter 55–89The user is now executing ROM 4 if it exists. If the ROM routinerequested does not exist the result is:PROGRAM NOT FOU
Operating FunctionsChapter 55–90CALL 73 disables the battery-backed RAM, prints “Battery BackupDisabled” when executed and allows a purging reset. The
Operating FunctionsChapter 55–91Example:For using protected variable storage area.A. Scalar VariablesPush all variables in one line:uPRINT MTOP 14335
Operating FunctionsChapter 55–92B. ArraysUse an array to set up the datauPRINT MTOP 14335 uPRINT MTOP-24 14311uPUSH 14311:REM NEW MTOP ADDRESS CALL 77
Introducing the BASIC ModuleChapter 22–3One RS-423A/232C/RS-422 compatible serial communications port(PERIPHERAL port), supporting bi-directional XON/
Operating FunctionsChapter 55–93The Active LED is on constantly during program execution or commandmode. When you issue a CALL 79 the Active LED remai
Operating FunctionsChapter 55–94You can use CALL 99 when printing out wide forms to reset the internalprint head character counter and prevent the aut
Operating FunctionsChapter 55–95CALL 119 resets the peripheral port to the following default settings:8 bits/character1 stop bitNo parityDCD offXON-XO
Chapter 6ProgrammingAfter reading this chapter you should be able to:program your BASIC Module for use with a programmable controller.use block-transf
ProgrammingChapter 66–2The BASIC Module also maintains a block-transfer-read (BTR) buffer thatis the value of the next block, read by the host process
ProgrammingChapter 66–3Refer to figure 6.1 for the sample ladder logic and figure 6.2 for thecorresponding BASIC program. The values shown in figure 6
ProgrammingChapter 66–4Figure 6.2Sample BASIC Module Programu5 DIM A(10) u10 REM SET BTW LENGTH TO 10 WORDS u20 PUSH 10: CALL 4 u30 REM SET BTR LEN
ProgrammingChapter 66–5You can use the following ladder logic program with PLC-3 or PLC-3/10processors. This program assumes that your application req
ProgrammingChapter 66–6Figure 6.5Sample PLC-3 Family Ladder Diagram6.4 PLC-3 Family Processors(continued)
ProgrammingChapter 66–7Rung 1 — Rung one is true only at power-up. It uses status word 3, bit 3(the AC power loss bit of the PLC-3) to zero the contro
IsolationG The Programming Port is isolated fromthe 1771 I/O backplane. (+500 V)G The Peripheral Port is isolated fromthe 1771 I/O backplane. (+500 V)
ProgrammingChapter 66–8Figure 6.6Sample PLC-5 Family Ladder Logic6.5 PLC-5 Family Processors(continued)
ProgrammingChapter 66–9Figure 6.7Sample PLC-5 Family Ladder LogicRungs 1 and 2 – Rungs 1 and 2 execute the BTR and BTW instructionsalternately. When t
ProgrammingChapter 66–101. The block lengths PUSHed for CALLs 4 and 5 must equal thecorresponding lengths on your BTW/BTR instructions in the processo
Chapter 7Data TypesThis chapter describes the data types and formats used by the BASICModule Data Conversion CALL routines. After reading this chapter
Data TypesChapter 77–2This value requires one word of the processor data table. The data isrepresented by a 3-digit binary coded decimal integer (figu
Data TypesChapter 77–3Figure 7.3Truncated 4-Digit BCD IntegerThis value requires one word of the processor data table. The data isrepresented by a 4-d
Data TypesChapter 77–4This value requires two words of the processor data table. The first wordcontains overflow, underflow and sign data and the thre
Data TypesChapter 77–5This value requires two words of the processor data table. The first wordcontains the overflow, underflow, sign data and the thr
Data TypesChapter 77–6The BASIC Module interfaces with the PLC-2, PLC-3 and PLC-5 familyprocessors. You can send the following data types to the BASIC
Chapter 8Editing A ProcedureAfter reading this chapter you should be able to make corrections ormodifications to your BASIC programs using the editing
Chapter 3Installing the BASIC ModuleThis chapter describes how to install your BASIC module in a 1771 I/Orack. After reading this chapter you should b
Editing A ProcedureChapter 88–2Invoke the insert command by typing [CTRL]A. This command insertstext at the cursor position. You must type a second [C
Editing A ProcedureChapter 88–3REN[NUM1],[NUM2] — begins at the start of the program andcontinues through the end of the program. The new line numbers
Editing A ProcedureChapter 88–4The following example shows you how to edit a simple procedure.Example:When the screen shows You do thisLIST10 EM10 REM
Chapter 9Error Messages and AnomaliesAfter reading this chapter you should be familiar with the module’s errormessages and anomalies.When BASIC is in
Error Messages and AnomaliesChapter 99–2ARITH. UNDERFLOW — An ARITH. UNDERFLOW occurs when anarithmetic operation exceeds the lower limit of a module
Error Messages and AnomaliesChapter 99–3EXTRA IGNORED — Error occurs when an INPUT statement requiringnumeric data, receives numeric data followed by
Error Messages and AnomaliesChapter 99–4IN ROM — The IN ROM message displays if you attempt to load a ROMprogram to tape with CALL 32 or 38. You shoul
Error Messages and AnomaliesChapter 99–5STRING# NOT ALLOCATED — This error occurs if you attempt toaccess a string that is outside the allocated strin
Error Messages and AnomaliesChapter 99–6BAD POSITION— This error occurs if you attempt to access a stringposition that is beyond the declared length o
Error Messages and AnomaliesChapter 99–7INVALID BAUD RATE ENTERED — This error occurs when a baud rateother than 300, 600, 1200, 2400, 4800, 9600 or 1
Installing the BASIC ModuleChapter 33–2Your module receives its power through the 1771 I/O chassis backplanefrom the chassis power supply. It does not
Error Messages and AnomaliesChapter 99–82. When using the variable I before an ELSE statement, put a space betweenthe I and the ELSE statement. If yo
Error Messages and AnomaliesChapter 99–99. If you use a VT100 terminal, the BASIC Module can miss an XONcharacter sent by your terminal when you enabl
Appendix AQuick Reference GuideMnemonic Page Description ExampleABS( )5–45 ABSOLUTE VALUE ABS(–3)ASC( ) 5–72 RETURNS INTEGER VALUE OF ASCII CHARACTER
Quick Reference GuideAppendix AA–2Mnemonic Page Description ExamplePH0 5–37 PRINT HEX MODE WITH ZERO SUPPRESSION PH0.APH1 5–37 PRINT HEX MODE WITH NO
Appendix BDecimal/Hexadecimal/Octal/ASCIIConversion TableColumn 1 Column 2 Column 3 Column 4DEC HEX OCT ASC DEC HEX OCT ASC DEC HEX OCT ASC DEC HEX OC
Appendix CBasic Module Programming HintsThese programming hints can help you to properly program your moduleto increase module performance.1. Always d
Publication 1771–6.5.34 July 1987Allen-Bradley, a Rockwell Automation Business, has been helping its customers improveproductivity and quality for mor
Installing the BASIC ModuleChapter 33–3Figure 3.1Keying Diagram for Placement of Module Keying BandsYou may change the position of these bands if subs
Installing the BASIC ModuleChapter 33–4Figure 3.2The Configuration PlugsAll other configuration plugs are factory set. Do not reset these factory setc
Installing the BASIC ModuleChapter 33–5Now that you have determined the configuration, power requirements,location, keying and wiring for your module,
Using This Manual 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Chapter Objectives 1. . . . . . . . . . . . . . . . . . . . .
Installing the BASIC ModuleChapter 33–6When the ACTIVE LED comes on observe the sign-on message displayedon the terminal followed by tREADY.You are no
Installing the BASIC ModuleChapter 33–7If the FLT LED lights after the module has been operating properly checkthe following troubleshooting chart. Pr
Installing the BASIC ModuleChapter 33–8Figure 3.4User PROM and Battery HolderTo replace the EPROM:1. Turn the small screw in the socket just above the
Installing the BASIC ModuleChapter 33–9Electrostatic discharge can damage integrated circuits or semiconductors inthis module if you touch backplane c
Installing the BASIC ModuleChapter 33–10The BAT LOW indicator should go out.You can monitor the battery low condition in revision A and revision Bmodu
Chapter 4Using the Serial PortsThis chapter describes how to use the program serial port and theperipheral serial port to connect terminals, Data Cart
Using the Serial PortsChapter 44–2CAUTION: Be sure you properly ground the system beforeturning on power. A difference in ground potential between th
Using the Serial PortsChapter 44–3The program port is an RS-423A/232C compatible serial port that providesminimum signal line connection to terminals,
Using the Serial PortsChapter 44–4Important: The program port always resets the most significant bit of allits data inputs. The range of each byte o
Using the Serial PortsChapter 44–5You can use an Industrial Terminal System as the programming system forthe BASIC Module. Connect the module to CHANN
Table of Contentsii4.3.4 Connecting a T50 Industrial Terminal (Cat. No. 1784-T50) to the Program Port I–9. . . . . . . . . . . . . . . . . . . . . .
Using the Serial PortsChapter 44–6You can connect a T30 Industrial Terminal to the BASIC Module programport to act as a dumb terminal.Refer to the fol
Using the Serial PortsChapter 44–74.3.4.1Configuring the SoftwareConfigure the driver package for compatibility with the BASIC Module bysetting:baud r
Using the Serial PortsChapter 44–8The peripheral port is an asynchronous serial communication channelcompatible with RS-423A/232C or RS-422 interfaces
Using the Serial PortsChapter 44–9Figure 4.7Cable Connection to SA/SB RecorderOutput Data – The BASIC Module stops sending characters within 2characte
Using the Serial PortsChapter 44–104.4.2.1 Hardware ConfigurationYou must configure the BASIC Module peripheral port and the T30Industrial Terminal se
Using the Serial PortsChapter 44–11You can use a 1770-SB Data Cartridge Recorder or 1770-SA DigitalCassette Recorder to save and load BASIC programs t
Using the Serial PortsChapter 44–12Figure 4.9Point-to-Point RS-422 ConnectionsFigure 4.10Multi-drop configuration with master and multiple slavesImpor
Using the Serial PortsChapter 44–13You must supply cables for connecting devices to the program andperipheral ports. You can construct the cables with
Chapter 5Operating FunctionsAfter reading this chapter you should be familiar with the BASICinstruction set and be ready to begin BASIC programming. T
Operating FunctionsChapter 55–2You may put more than one statement on a line, if separated by acolon (:). You can use only one statement number per li
Table of Contents iii5.3.12 Command: XFER 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.13 Command: PROG 12. . . . . . . . . . .
Operating FunctionsChapter 55–3A constant is a real number that ranges from +1E–127 to +.99999999E+127. A constant can be an integer. We refer to cons
Operating FunctionsChapter 55–4Important: The BASIC Module requires less time to find a scalarvariable because there is no expression to evaluate. I
Operating FunctionsChapter 55–5The argument stack (A-stack) stores all constants that the BASIC Moduleis currently using. Operations such as add, subt
Operating FunctionsChapter 55–6The following sections list and describe the commands you canuse with the BASIC Module.Action Taken: After you type RUN
Operating FunctionsChapter 55–7Action Taken: If you stop a program by typing a Control C on theconsole device or by execution of a STOP statement, you
Operating FunctionsChapter 55–8Variations: Two variations of the LIST command are possible with theBASIC Module.They are:1. LIST [ln num] (cr) and2. L
Operating FunctionsChapter 55–9Action taken: When you enter NEW(cr), the BASIC Module deletesthe program that is currently stored in RAM memory. In ad
Operating FunctionsChapter 55–10Action taken: This command interrupts the scrolling of a BASICprogram during the execution of a LIST command. It also
Operating FunctionsChapter 55–115.3.11.1 RAMWhen you enter RAM(cr), the BASIC Module selects the currentprogram from RAM MEMORY.Important: RAM space
Operating FunctionsChapter 55–12Action taken: The XFER (transfer) command transfers the currentselected program in EPROM to RAM and then selects the R
Table of Contentsiv5.4.26 Statement: POP[var] 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4.27 Statement: REM 40. . . . . . . . . .
Operating FunctionsChapter 55–13Example:uLIST10 FOR I=1 TO 10 20 PRINT I 30 NEXT I 40 END READY uCALL 8 :REM DISABLE INTERRUPTS uPROG 12uREADY CALL 9
Operating FunctionsChapter 55–14Action taken: You can use the PROG1 command to program theresident EPROM with baud rate information. When the module i
Operating FunctionsChapter 55–15Figure 5.1Flow Chart of Power-up OperationFigure 5.1 shows BASIC Module operation from a power-up conditionusing PROG1
Operating FunctionsChapter 55–16The following sections list and describe the statements you can usewith the BASIC Module.Mode: COMMAND AND/ OR RUN Typ
Operating FunctionsChapter 55–17Mode: COMMAND/RUNType: CONTROLThe CLEARS statement resets all of the module’s stacks. Thecontrol, argument and interna
Operating FunctionsChapter 55–18Mode: RUNType: AssignmentDATADATA specifies expressions that you can retrieve using a READ statement.If multiple expre
Operating FunctionsChapter 55–19Mode: COMMAND AND/OR RUN Type: AssignmentDIM reserves storage for matrices. The storage area is first assumed tobe zer
Operating FunctionsChapter 55–20Examples:SIMPLE DO-UNTILu10 A=0u20 DOu30 A=A+1 u40 PRINT Au50 UNTIL A=4u60 PRINT “DONE”u70 ENDuRUN1234DONEREADYuNESTED
Operating FunctionsChapter 55–21Mode: RUN Type: CONTROLThe DO – WHILE [rel expr] instruction provides a means of “loopcontrol” within a module program
Operating FunctionsChapter 55–22Mode: RUN Type: CONTROLThe END statement terminates program execution. The continue command, CONT does not operate if
Table of Contents v5.7.10.2 Internal Floating Point to 16-Bit Unsigned Binary (4 digit hex) – CALL 21 57. . . . . . . . . . . . . . . . . . . . . .
Operating FunctionsChapter 55–23Since B=0, C=10 and D=2, the PRINT statement at line 20 executes6 times. The values of “A” printed are 0, 2, 4, 6, 8 a
Operating FunctionsChapter 55–24RETURNUse this statement to “return” control to the statement following themost recently executed GO SUB STATEMENT. Us
Operating FunctionsChapter 55–25Unlike the RUN command the GOTO statement, if executed in theCOMMAND mode, does not clear the variable storage spac
Operating FunctionsChapter 55–26Upon execution of line 10 IF A is equal to 100, THEN A is assigned avalue of 0. IF A does not equal 100, A is assigned
Operating FunctionsChapter 55–27Causes a question mark (?) to print on the console device. Thisprompts you to input two numbers separated by a comma.
Operating FunctionsChapter 55–28Examples: u10 STRING 110,10 u10 STRING 110,10u20 INPUT “NAME:”,$(1) u20 INPUT “NAMES:”,$(1),$(2)u30 PRINT “HI”,$(1) u3
Operating FunctionsChapter 55–29Mode: COMMAND AND/OR RUNType: ASSIGNMENTUse the LET statement to assign a variable to the value of anexpression. The g
Operating FunctionsChapter 55–30Mode: RUN Type: CONTROLThe ONERR[ln num] statement lets you handle arithmetic errors, ifthey occur, during program exe
Operating FunctionsChapter 55–31Mode: RUN Type: CONTROLYour BASIC Module can process a line in milliseconds while thetimer/counters on the microproces
Operating FunctionsChapter 55–32If you do not want this delay, you should assign a variable to the specialfunction operator, TIME, at the beginning of
Table of Contentsvi5.10.3.2 String Append (Concatenation) – CALL 61 81. . . . . . . . . . 5.10.3.3 Number to String Conversion – CALL 62 81. . . .
Operating FunctionsChapter 55–33The following sections list and describe the special print formattingstatements.5.4.22.1 PRINT TAB([expr])Use the TAB(
Operating FunctionsChapter 55–345.4.22.4 PRINT USING (special characters)Use the USING function to tell the BASIC Module what format to usewhen displa
Operating FunctionsChapter 55–355.4.22.6 PRINT USING(#.#) This forces the module to output all numbers using an integer and/orfraction format. The num
Operating FunctionsChapter 55–365.4.22.8 Reset Print Head Pointer – CALL 99 You can use CALL 99 when printing out wide forms to reset the internalprin
Operating FunctionsChapter 55–37Mode: COMMAND and/or RUN Type: INPUT/OUTPUTThe PH0. and PH1. statements function the same as the PRINT statementexcept
Operating FunctionsChapter 55–38Mode: COMMAND AND/OR RUN Type: ASSIGNMENTThe arithmetic expression, or expressions, following the PUSH statementare ev
Operating FunctionsChapter 55–39Mode: COMMAND AND/OR RUNTYPE: ASSIGNMENTThe value on top of the ARGUMENT STACK is assigned to the variablefollowing t
Operating FunctionsChapter 55–40Mode: COMMAND and/or RUN Type: CONTROL – Performs no operationREM is short for REMark. REM allows you to add comments
Operating FunctionsChapter 55–41Mode: RUN Type: CONTROLUse the RETI statement to exit from the ONTIME interrupts that arehandled by a BASIC Module pro
Operating FunctionsChapter 55–42Note that the line number printed out after execution of the STOPstatement, is the line number following the STOP stat
Table of Contents viiData Types 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1 Chapter Objectives 1. . . . . . . .
Operating FunctionsChapter 55–43The BASIC Module contains a complete set of arithmetic and logicaloperators. We divide the operators into two groups,
Operating FunctionsChapter 55–445.5.1.1 Comments on logical operators .AND.,.OR. and .XOR.These operators perform a BIT-WISE logical function on valid
Operating FunctionsChapter 55–45We divide the unary operators into three groups; general purpose, logfunctions and trig functions.5.5.2.1 General Purp
Operating FunctionsChapter 55–465.5.2.1.6 RND Returns a pseudo-random number in the range between 0 and 1 inclusive.The RND operator uses a 16-bit bin
Operating FunctionsChapter 55–475.5.2.3.2 COS([expr])Returns the cosine of the argument. The argument is expressed in radians.Calculations are carried
Operating FunctionsChapter 55–48Although this method of angle reduction provides a simple and economicalmeans of generating the appropriate arguments
Operating FunctionsChapter 55–49Relational expressions involve the operators =, tu, u, u=, t, and t=.These operators are typically used to “test” a co
Operating FunctionsChapter 55–50Special operators include special function operators and system controlvalues.Special function operators directly mani
Operating FunctionsChapter 55–51When TIME is assigned a value with a LET statement (i.e. TIME u 100),only the integer portion of TIME is changed.Examp
Operating FunctionsChapter 55–52The system control values determine how memory is allocated by theBASIC Module.5.6.2.1 MTOPAfter reset, the BASIC Modu
Chapter 1Using This ManualRead this chapter before you use the BASIC Module. It tells you how touse this manual properly and efficiently.This manual s
Operating FunctionsChapter 55–53Example:u10 REM PRINT CONTENTS OF BTW BUFFER u20 C=(XBY(7D0AH)*100H)+XBY(7D0BH) u30 FOR I=0 TO 128 u40 PH0. XBY(C+I),
Operating FunctionsChapter 55–54This routine sets the number of words (1–64) to transfer between theBASIC Module and the host processor. The processor
Operating FunctionsChapter 55–55Important: You must use an Interrupt Control CALL 9 after a PROGcommand to re-enable interrupts. This routine enable
Operating FunctionsChapter 55–565.7.9.4 6-Digit, Signed, Fixed Decimal BCD to Internal Floating Point"XXXXXX – CALL 13 The input argument is the
Operating FunctionsChapter 55–575.7.10.1 Internal Floating Point to 3-Digit, Signed, Fixed Decimal BCD "XXX –CALL 20This routine has two input ar
Operating FunctionsChapter 55–585.7.10.4 Internal Floating Point to 6-Digit, Signed, Fixed Decimal BCD"XXXXXX – CALL 23 This routine converts an
Operating FunctionsChapter 55–59The peripheral port is used for:1. exchanging data with an external device with user written protocol.2. listing progr
Operating FunctionsChapter 55–60The five values PUSHed on the stack before executing the CALL are in thefollowing order: Parameter SelectionsNumber of
Operating FunctionsChapter 55–61Important: Maximum baud rate is 2400 bps for all data recorder CALLroutines. The Peripheral Port is set up in these
Operating FunctionsChapter 55–62Press PLAY. Tape movement begins and the recorder searches for thebeginning of the next program. As each line of the p