Publication 1769-UM001B-EN-P - October 2002
Explicit Messaging Application Examples B-31
Discrete Module
Configuration Files
The following configuration information applies to these modules:
The read/writable configuration data file allows the setup of the hold
last state and user-defined state conditions.
The manipulation of the bits from this file is normally done with
programming software (e.g. RSLogix 500, RSNetworx for DeviceNet,
etc.) during initial configuration of the system. In that case, graphical
screens are provided via the programmer to simplify configuration.
However, some systems (e.g. 1769-ADN DeviceNet adapter) also
allow the bits to be altered as part of the control program using
communication rungs. In that case, it is necessary to understand the
bit arrangement.
Data Table File N11 (Shown in Hexadecimal Radix)
Offset0123456789
N11:01016E1330CA170000
N11:10 101 16 1013 30C A 1A 8304 8304 1862 1862
N11:20 1862 1862 00000000
N11:301016E1330CA1A0000
N11:404000010141613 F 0
N11:50 101 2 8E13 8000000
1769-OA8 1769-IQ6XOW4
1769-OB16 1769-OW8
1769-OV16 1769-OW8I
Word
Bit Position
1514131211109876543210
0000000000000000PFE
1 Program State
1
for Output Array Word 0
2 Program Value
2
for Output Array Word 0
3 Fault State
3
for Output Array Word 0
4 Fault Value
4
for Output Array Word 0
1 Program State Word (word 1) selects the hold last state or user-defined safe state condition on a
system transition from Run to Program. User-Defined Safe State = Bit Setting 0 and Hold Last State
= Bit Setting 1
2 Program Value Word (word 2) is used to program the user-defined safe state value (0 = Off, 1 = On).
Each output is individually configurable for on or off.
3 Fault State Word (word 3) selects the hold last state or user-defined safe state condition on a
system transition from Run to Fault. User-Defined Safe State = Bit Setting 0 and Hold Last State
= Bit Setting 1
4 Fault Value Word (word 4) is used to program the fault state value (0 = Off, 1 = On). Each output is
individually configurable for on or off. Off = Bit Setting 0 and On = Bit Setting 1