Publication 1769-UM001B-EN-P - October 2002
Configuring Your Compact I/O Series B DeviceNet Adapter 4-23
4. From the Configuration Settings tab, double-click on a Channel
to configure it.
You will see a screen similar to this one.
For details on these options, refer to the Compact 1769 Analog
I/O User Manual, publication 1769-6.0.
5. Choose OK.
You can configure Channel 0
to Disable or Enable.
You can configure the
Program State parameter to
Hold Last State or
User-Defined Value.
You can configure the Output
Range parameter to (-10 to
+10V dc),
(0 to 5V dc), (0 to 10V dc),
(4 to 20mA), or (1 to 5V dc).
You can configure the Data Format
parameter to Raw/Proportional
Data, Engineering Units,
Scaled-for-PID, or Percent Range.
You can configure
Communication Failure
parameter to Leave Outputs in
Program Mode or Change
Outputs to Fault Mode.
You can configure the Fault
State parameter to Hold Last
State or User-Defined Value.