Publication 1769-UM001B-EN-P - October 2002
2-14 How Communication Takes Place and I/O Image Table Mapping
1769-OW8I Individually
Isolated AC/DC Relay
Output Module (8 Point)
Output Data
For each 1769-OW8I module, output data word 0 contains the control
program’s directed state of the discrete output points. Bits 8 to 15 are
not used.
Input Data
For each 1769-OW8I module, input data word 0 contains the state of
the module’s output data (output data echo). During normal operation
(controller in Run), these input bits represent the logic state that the
outputs are directed to by the control program. They are also
dependent upon the:
Program Mode configuration (Hold Last or User-Defined Safe
State)
Fault Mode configuration (Hold Last or User-Defined Safe State)
For the 1769-OW8I, input data word 0 bits 8 to 15 are not used.
Word
Bit Position
1514131211109876543210
0
0 0 0 0 0 0 0 0 wwwwwwww
w = write
Word
Bit Position
1514131211109876543210
0
0 0 0 0 0 0 0 0rrrrrrrr
r = read
IMPORTANT
The output module’s input data reflects the output
data echo of the module, not necessarily the
electrical state of the output terminals. It does not
reflect shorted or open outputs.