
88 Rockwell Automation Publication 1769-UM012B-EN-P - January 2014
Appendix A Configure the 1769-ASCII Module as a Generic Module
6. Open the controller tags for monitor to enter the following configuration
parameters in the Local:<slot>:C tag data members.
All other parameters are 0.
This is a controller-scoped configuration tag.
Data [ ] Word Value (Decimal) Meaning
00 Alternating mode
1 3 Framing is 8N1
2 0 9600 baud
3 80 Max Rx Characters
6 1 Use an Rx End delimiter, but exclude it from the input buffer
7 13 Use a Carriage Return as the Rx End delimiter
10 1 Produce data when available
12 80 Max Tx Characters
Comentarios a estos manuales