98 Rockwell Automation Publication 1769-UM012B-EN-P - January 2014
Appendix C Error Codes
This table indicates the error codes that are associated with Channel 0.
Table 12 - Channel 0 Module Configuration Errors
Value
(Hex)
Meaning Description
430 Data buffer mode 0 = alternate mode; 1 = simultaneous mode. Anything
else is invalid.
440 Invalid serial port framing The serial port framing specified is invalid.
441 Invalid serial port speed The serial port speed specified is invalid.
442 Invalid max number of receive characters The maximum number of receive characters specified for
channel 0 is too large.
443 Invalid receive record mode The receive record mode specified is invalid.
444 Invalid receive start delimiter The receive start delimiter specified is invalid.
445 Invalid receive record end mode The receive record end mode specified is invalid.
446 Invalid receive record end delimiter The receive record end delimiter specified is invalid.
447 Invalid pad character The pad character specified is invalid.
448 Invalid receive swap mode The receive swap mode specified is invalid.
449 Invalid master handshake mode The master handshake mode specified is invalid.
44A Invalid message timeout The timeout delay specified is invalid.
44B Invalid max number of transmit characters The transmit characters specified is invalid.
44C Invalid transmit record end mode The transmit record end mode specified is invalid.
44D Invalid transmit end delimiter The transmit end delimiter specified is invalid.
44E Invalid transmit swap mode The transmit swap mode specified is invalid.
44F-47F Undefined channel 0 error An undefined error has occurred.frogProduct group /