Publication 1769-RM016A-EN-P - July 2006
Module Data, Status, and Configuration 57
Each output's duration time is configured using one word in the configuration
data file. For OUT0, output duration is configured using bits 0…9 of word 14.
Configure the output duration for OUT1 with word 22; for OUT2 use word
30 and, for OUT3 use word 38. The following table shows the bits patterns to
use to configure output duration time.
The default duration time setting is 0, no set duration time. The output
remains ON only if the Boolean expression remains TRUE.
Refer to Output Delay and Duration Operation on page 18, for additional
information on the module's duration time operation.
Output Duration Time Bit Patterns
Words 14, 22, 30, 38 Duration Time
(ms)
Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0000000000
(1)
**
(1)
The output remains ON only if the Boolean expression remains TRUE.
0000000001 1
0000000010 2
0000000011 3
0000000100 4
1111100011 995
1111100100 996
1111100101 997
1111100110 998
1111100111 999
1111101000 1000