Rockwell-automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command Manual de usuario Pagina 175

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 251
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 174
10–4 Diagnostic Status Information
Publication
17706.5.16 - October 1996
1747L532, L541, L542, L543 (SLC 5/03 and SLC 5/04
processors) Status Bytes
Bytes Bits Contents Description
1
05
mode/status
00
6 testing edits
7 edits in processor
2 07 type extender EE
3 07 extended interface type
20 = DH485 on port 0 (RS232)
31 = DH+ on port 1 via domino plug
34 = DF1 fullduplex protocol on port 0
36 = DF1 halfduplex protocol on port 0
4 07 extended processor type
49 = rack type 1747L534
5B = rack type 1747L534
5
04
series/revision
= 0 firmware release1
= 1 firmware release 2, etc.
57 = 0 series A
= 1 series B, etc.
6 - 16 all bulletin number/name
(in ASCII)
5/03 = 1747L532
5/04 = 1747L542
Productspecific Information
17 all major error word low byte
18 all major error word high byte
19
04
processor mode
status/control word
00000 = download
00001 = remote PROG
00011 = idle due to SUS instruction
00110 = remote RUN
00111 = remote TEST; continuous scan
01000 = remote TEST; single scan
01001 = remote TEST; continuous step
10000 = download
10001 = PROG
11011 = idle due to SUS instruction
11110 = RUN
5 forces active
6 forces installed
7 communication active
20
0
processor mode status/control
protection power loss
1
p
word (high byte)
startup protect fault
2 load memory module on error
3 load memory module always
4 load memory module and run
5 major error  processor halted
6 locked
7 first pass bit
21 07
program ID
low byte
22 07
pg
high byte
23 07 processor RAM size (in Kbytes)
Vista de pagina 174