Rockwell-automation 1771-IFE/C INSTL.INSTRUCTIONS ANALOG INPU Manual de usuario Pagina 11

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 16
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 10
Analog Input Module 11
Publication
17715.45 - July 1997
Use the following table to read data from your input module.
Dec. Bits 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Description
Octal Bits 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Description
Word 1 HF EE CS RTS IS OR PU Diagnostics
Hardware fault - (HF) When this bit is set, the dc/dc
converter fuse has blown. Digital logic will continue
to operate.
EEPROM status bit - (EE) This bit is set if an error occurs
saving calibration data to nonvolatile memory. If this bit is set
at powerup, the data from the EEPROM did not pass the
checksum and no calibration values are used.
Calibration status bit - (CS) When calibrating the
module, this bit will be cleared if the calibration was
successful. If the bit is set, an incorrect voltage/current
was applied, or offset and gain calibrations were
attempted simultaneously.
Real time sample fault bit - (RTS) This bit is set if the module is
configured for RTS and a block transfer read has not occurred within
the user-programmed period.
Power up bit - (PU) Used by the
module to tell the processor that it is
alive but not yet configured. It is a key
element in the application program.
Out of range bit - (OR) This bit is sent to
tell the processor that one or more
channels are either over or under range.
1
Invalid scaling bit - (IS) This bit reports that the
scaling is somehow invalid. Usually, both values
are equal or minimum is greater than maximum
when this bit comes on. Can also be an invalid
filter value.
Octal Bits 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 Description
2 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Data underrange for channels 1-16
3 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Data overrange for channels 1-16
Underrange bits for each channel. Bit 00 for channel 1, bit 01 for channel 2, etc.
1
These
1
to 5V dc, 4 to 20mA (default)
U
n
d
errange
bi
ts
f
or eac
h
c
h
anne
l
.
Bi
t
00
f
or c
h
anne
l
1
,
bi
t
01
f
or c
h
anne
l
2
, etc.
1
Th
ese
bits are set (1) at approximately the input range limits shown on the right.
0
to 5V dc, 0 to 20mA
bits are set (1) at approximately the input range limits shown on the right.
Overrange bits for each channel. Bit 00 for channel 1, bit 01 for channel 2, etc.
1
These
bits are set (1) at approximately the input range limits shown on the right
5 to +5V dc, 20 to +20mA
g ,,
bits are set (1) at approximately the input range limits shown on the right.
10 to +10V dc, 0 to 10V dc
4 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Polarity bits - Set when input is less than zero. Bit 00 for channel 1, bit 01 for channel
2, etc.
Data polarity for channels 1-16
5 Channel 1 Input Channel 1 Input
6 Channel 2 Input Channel 2 Input
7 Channel 3 Input Channel 3 Input
8 Channel 4 Input Channel 4 Input
⇓⇓
20 Channel 16 Input Channel 16 Input
21 Offset calibration results bits - Each bit represents a channel. After a calibration BTW
has been sent, the module confirms calibration by echoing back the channels that were
calibrated during the offset calibration BTW. In differential mode, channels 09 thru 16
are zero.
Offset Calibration Results
22 Gain calibration results bits - Each bit represents a channel. After a calibration BTW
has been sent, the module confirms calibration by echoing back the channels that were
calibrated during the gain calibration BTW. In differential mode, channels 09 thru 16
are zero.
Gain Calibration Results
1
Attention: If
an input terminal'
s voltage exceeds +
14.25V as referenced to module common, channeltochannel crosstalk can cause invalid input readings and invalid
underrange/overrange bits.
Vista de pagina 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16

Comentarios a estos manuales