Rockwell-automation 1771-IFE/C INSTL.INSTRUCTIONS ANALOG INPU Manual de usuario Pagina 6

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 16
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 5
Analog Input Module6
Publication
17715.45 - July 1997
Connect your I/O devices to the cat. no. 1771-WG wiring arm
shipped with the module.
!
ATTENTION: Remove power from the 1771 I/O
chassis backplane and field wiring arm before
removing or installing an I/O module.
Failure to remove power from the backplane or
wiring arm could cause module damage, degradation
of performance, or injury.
Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.
Input connections for the 1771-IFE module with:
single-ended inputs are shown on page 7
differential inputs are shown on page 8
Minimizing Ground Loops
To minimize ground-loop currents on input circuits:
use single-ended mode whenever possible
use 2-wire transmitters with a common power supply
separate 2-wire and 4-wire transmitters between different
modules
tie 4-wire transmitter and/or separate power supply grounds
together
Important: We do not recommend mixing 2-wire and 4-wire
transmitter inputs on the same module. Power supply
placement can make it impossible to eliminate ground
loops.
Cable Lengths
Recommended maximum cable length for voltage-mode input
devices is 50 feet. This recommendation is based on considerations
of signal degradation and electrical noise immunity in typical
industrial environments. Cable length for current-mode input
devices need not be as restrictive because analog signals from these
devices are less sensitive to electrical noise interference.
Connect Wiring to the
Field Wiring Arm
Vista de pagina 5
1 2 3 4 5 6 7 8 9 10 11 ... 15 16

Comentarios a estos manuales

Sin comentarios