Rockwell-automation 1791-XXXX Discrete I/O AC and DC Block I/O Input a Manual de usuario Pagina 38

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 98
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 37
Installing Block I/O
Chapter 3
3-19
Connections
1791-24AR Series B Connector/Terminal
Connections
Designation Description Left Conn. Right Conn.
Power
L1 ac hot 1
Power
Connections
N
ac neutral 3
GND Chassis ground 2
1
Remote I/O
BLU Blue wire - RIO 6
Remote
I/O
Connections
CLR
Clear wire - RIO 8
SHD Shield - RIO 7
I/O Connections
in 00 thru in 07 Input 00 thru 07
16, 18, 20,
22, 24, 26,
28, 30
Input
COM 1
L2/N Input Common 10, 12, 14
2
Input
(G)
6
COM 2 L2/N Input Common 9, 11, 13
3
PLC: in 10 thru in 17
SLC: in 08 thru in 15
PLC: Input 10 thru 17
SLC: Input 08 thru 15
15, 17, 19,
21, 23, 25,
27, 29
Input
(G+1)
7
in 00 thru in 07 Input 00 thru 07
15, 13, 11, 9, 7, 5,
3, 1
(G+1)
7
COM 3 L2/N Input Common 21, 19, 17
4
Output
Vac/dc 4 ac or dc Output Supply 22, 20, 18
5
Output
(G)
8
PLC: out 00 thru out 07
SLC: out 00 thru out 07
PLC: Output 00 thru 07
SLC: Output 00 thru 07
16, 14, 12, 10, 8,
6, 4, 2
Not used
For internal test only;
not for customer use.
4, 5 29, 27, 26
No Conn
No internal connection;
customer can use.
30, 28, 25, 24, 23
1
Connect chassis ground to equipment grounding stud. These are not internally connected.
2
Left connector terminals 10, 12 and 14 are internally connected together
.
3
Left connector terminals 9, 11 and 13 are internally connected together
.
4
Right connector terminals 21, 19 and 17 are internally connected together
.
5
Right connector terminals 22, 20 and 18 must be externally connected to accommodate total amperage.
6
IN (G) = input module group (1 word).
7
IN (G+1) = input module group plus 1 word.
8
OUT (G) = output module group (1 word).
Vista de pagina 37