Installing Block I/O
Chapter 3
3-21
Figure 3.15
Output
W
iring Connections for the 17910B16
Series
B
RIO
1
30
PLC
24V
dc
24V dc
24V dc
+
+
+
GND
NOT
USED
NOT
USED
BLU
SHD
CLR
RET
2
Vdc
2
out 00
RET
1
Vdc
1
out 01
out 02
out 03
out 04
out 05
out 06
out 07
Vdc
2
out 10
out 12
out 13
out 14
out 15
out 16
out 1
1
Vdc
1
out 17
+24
RET
+24
RIO
1
30
SLC
24V dc
24V dc
24V dc
+
+
+
GND
NOT
USED
NOT
USED
BLU
SHD
CLR
RET
2
Vdc
2
out 00
RET
1
Vdc
1
out 01
out 02
out 03
out 04
out 05
out 06
out 07
Vdc
2
out 08
out 10
out 1
1
out 12
out 13
out 14
out 09
Vdc
1
out 15
+24
RET
+24
Note:Vdc
1 connections must be externally connected together to accommodate amperage rating.
Vdc 2 connections must be externally connected together to accommodate amperage rating.
Output fusing is recommended. Refer to
Table 2.B
on page
28.
1
2
1
2
29
30
29
30
Connections
17910B16
Series
B
Connections
Designation Description Terminal No.
Power
+24 +24V dc Power 1
Power
Connections
RET +24
dc Return 3
GND Chassis ground 2
1
Remote I/O
BLU Blue wire RIO 6
Remote I/O
Connections
CLR
Clear wire RIO 8
SHD Shield RIO 7
I/O Connections
out 00 thru out 07 Output 00 thru 07 16, 18, 20, 22, 24, 26, 28, 30
Output
Vdc 1
+24V dc output supply 12, 14
2
p
RET 1 dc output return 10
Vdc 2 +24V dc output supply 11, 13
3
Output
RET 2
dc output return 9
Output
PLC: out 10 thru out 17
SLC: out 08 thru out 15
PLC: Output 10 thru 17
SLC: Output 08 thru 15
15, 17, 19, 21, 23, 25, 27, 29
Not used
For internal test only; not
for customer use.
4, 5
1
Connect chassis ground to equipment grounding stud. These are not internally connected.
2
T
erminals 12 and 14 must be externally connected by customer to accommodate amperage rating.
3
T
erminals 1
1 and 13 must be externally connected by customer to accommodate amperage rating.