SW1
SW2
Open cover to
access switches
1
30
179116B0
24V
dc INPUT
INPUT INPUT
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
12403-I
87654321
01
87654321
01
Position = 1Position = 0
End View
NOTE:
Default Switch
Settings = 0
Set switch SW2-3 to 0 if this rack will have a unique
address (not complemented). If this rack address is a
duplicate of another I/O block or chassis, set the switch to
1 for primary or 0 for complementary. Refer to Table 4.G
for the complementary I/O rack address.
Only block I/O modules with all inputs or all
outputs can use complementary I/O.
Series A block I/O modules do not support
complementary I/O. If using series A modules, set
this switch to 0.
ATTENTION: Cycle power to the module after setting the switches.
Configuring Your Block I/O for PLC
Family Programmable Controllers
Chapter 4
4-2
Figure 4.1
Switch
Settings for the ac and dc Block I/O Modules (16point illustrated)
SW2-8
NotusedNot used
dc Applications ac Applications
SW2-7 Filter Speed Select SW2-7
0 Slow
1 Fast
Not Used
Note: For inputs only
SW2-6 Last I/O Group
0 Not last rack
1 Last rack
SW2-5
Processor
Restart/Lockout (PRL)
0 Processor Restart
1 Processor Lockout
SW2-4 Hold Last State
0 Reset Outputs
1 Hold Last State
SW2-3 Complementary I/O
1
0 NonCompleted Systems
0 Complementary Rack
1
1 Primary Rack
1
1
See Note.
Communication Rate
SW2-2 SW2-1 Bits/s
0 0 57.6 K
0 1 115.2 K
1 0 230.4 K
1 1 230.4 K
SW1-3 thru 8 Rack Address
Refer to Table 4.F for settings.
Starting Quarter
SW1-2 SW1-1 Module Group
0 0 0 (1st)
0 1 2 (2nd)
1 0 4 (3rd)
1 1 6 (4th)
Comentarios a estos manuales