ArmorBlock-LP 8 Output Module8
Publication
1792-5.7 – December 1997
Refer to the table below for the word/bit definitions.
Bit 07 06 05 04 03 02 01 00
Consumes O8A O7A O6A O5A O4A O3A O2A O1A
Produces Reser
ved
OF Reserved
Where: O = Output
OF = Output fault status
Word Bit Description
Consumes 00–07 Output bits – when the bit is set (1), the output is on. Bit 00
corresponds to output 1A, bit 01 corresponds to output 2A, bit 02 to
output 3A, bit 03 output 4A, bit 04 corresponds to output 5A, bit 05
to output 6A, bit 06 to output 7A, and bit 07 to output 8A.
Produces
00–05 Reserved
Produces
06 OF = output fault status bit – indicates presence of field power and
overload condition.
07 Reserved
Troubleshoot with the Indicators
The ArmorBlock I/O module has the following indicators:
Network status indicators (NS)
Module status indicator (MS)
Individual Output status indicators A1 through A8
Power Status indicators