High Current 8 Input/8 Output ArmorBlock I/O Module Series B 11
Publication 1792D-IN005D-EN-P - February 2002
Troubleshoot with the Indicators
This module has the following indicators:
Network/Module status indicator
Logic status indicators
Individual point status indicators
The following illustration shows status indicators.
The following table describes the network and module status
indicator.
Net/Mod Status Indicator
Indication Status
Off No power or auto bauding
Flashing Green/Off On line but not connected
Solid Green On line, link OK, connected
Flashing Red Recoverable fault-expansion module fault or module
configuration error
I/O connection fault-one or more I/O connections in
the timed-out state
Solid Red Unrecoverable fault
Communication failure-duplicate node address present
or incorrect baud rate
Green to Red to Off At powerup only - LED test
Status Indicators
42287