14 High Current 8 Input/8 Output ArmorBlock I/O Module Series B
Publication 1792D-IN005D-EN-P - February 2002
General Specifications
Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
–20 to 60°C (–4 to 140°F)
Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry
Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
–40 to 85°C (–40 to 185°F)
Wiring Category
DeviceNet Conductors
Category
Use 14-22 AWG wire with insulation
Temperature rating of 75°C min.
See Publication DN-6.7.2
2
1, 2
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5 to 95% non-condensing
Shock Operating IEC60068-2-27: Test Ea (Unpackaged shock, ES#002)
Operating 30g
Non-operating 50g
Vibration IEC60068-2-6 (Test Fc, Operating):
10g @ 10-500Hz
Emissions CISPR 11:
Group 1, Class A
ESD Immunity IEC 61000-4-2:
4kV contact discharges
8kV air discharges
Enclosure Type Rating Meets IP52
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to
1000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
EFT/B Immunity IEC 61000-4-4:
±2kV at 5kHz on signal ports
Surge Transient Immunity ±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports
+
2kV line-earth (CM) on shielded ports
Conducted RF Immunity IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz
Comentarios a estos manuales