Specifications - 2 Input/2 Protected Output Module Cat. No. 1793-IB2XOB2P
and -IB2XOB2PS
Module Type 2 input/2 output digital combination w/electronic fusing
1793-IB2XOB2P - screw-clamp terminations
1793-IB2XOB2PS - spring-clamp terminations
Module Location DIN rail mounting
Number of Channels 2 digital input - sinking/2 digital output - sourcing,
protected
Input
On-state Voltage 10-31.2V dc; 24V dc nominal
On-state Current 2-12 mA; 8mA @ 24V dc
Off-state Voltage 5V dc maximum
Off-state Current 1.5mA minimum
Channel Impedance 4.6K
Ω
Isolation Voltage Channel to system - 850V dc for 1s
Channel to channel - None
Input Delay - selectable
Off to On
On to Off
512
μ
s, 1, 2, 8, 16, 32 or 64ms
512
μ
s, 1, 2, 8, 16, 32 or 64ms
Default = 512
μ
s
Output
On-state Voltage 10-31.2V dc; 24V dc nominal
On-state Current 1-500mA per channel
Off-state Voltage 31.2V dc maximum
Off-state Current 0.5mA maximum leakage
Channel Impedance 1.0
Ω
(0.5V dc maximum drop)
Surge Current 1.5A for 50ms, repeatable every 2s
Isolation Voltage Channel to system - 850V dc for 1s
Channel to channel - None
Delay Time Off to On
On to Off
0.5ms maximum
1.0ms maximum
General
Flexbus Current 20mA maximum
Power Dissipation 1.4W @ 31.2V dc
Thermal Dissipation 4.8 BTU/hr @ 31.2V dc
Indicators 4 yellow channel status indicators