FLEX I/O Isolated Input HART Analog Module 15
Publication
1794-IN115C-EN-P - April 2009
29…
32
Words 9…12 for channel 5
33…
36
Words 9…12 for channel 6
37…
40
Words 9…12 for channel 7
41 Reserved C
7
C
6
C
5
C
4
C
3
C
2
C
1
C
0
Note: Reserved data may not be shown in certain controller software
(1)
not shown or used in RSLogix 5000.
Configuration Map descriptions
BOA
BOB
Byte order group A
Byte order group B
Byte order group A and B values must
match each other.
Refer to the Byte Order table
FLTRn Channel n Digital Filter Refer to Channel Digital Filter table
Fn Fault mode channel n 0: Local/Remote
faults disabled
1: Enabled
CHn HART
Current Ratio
HART current fault ratio limit
on channel n
Valid values are 0, or 5…31 percent of
full scale. A value of 0 disables this
feature. Refer to the HART Current
Ratio table for more information.
DHn Disable HART
communications on channel n
0: HART
communications
enabled
1: HART
communications
disabled
Configuration Map
Word Bit
1514131211109876543210