18 FLEX I/O Isolated Input HART Analog Module
Publication
1794-IN115C-EN-P - April 2009
Channel Data Formats
Format
(1)
Bits Format
Name
Signal Range User Range Resolution
15 14 13 12
11 10 9 8
7654
LO HI LO HI
3210
0 0000020 mA in
Milliamps
0.00 22.00 0
(0.000 mA)
22000
(22.000 mA)
1.0 µA
1 0001020 mA in
% Full Scale
0.00 22.00 0
(0%)
11000
(110.00%)
2.0 µA
3 0011020 mA in
UINT
0.00 20.00 0 65535 0.3052 µA
4
(2)
0100420 mA in
Milliamps
2.00 22.00 2000
(2.000 mA)
22000
(22.000 mA)
1.0 µA
5
(2)
0101420 mA in
% Full Scale
2.00 22.00 -1250
(-12.50%)
11250
(112.50%)
1.6 µA
7
(2)
0111420 mA in
UINT
4.00 20.00 0 65535 0.2441 µA
(1)
All other formats are invalid.
(2)
HART Communications supported with these data formats only.