Rockwell Automation Publication 20P-IN009D-EN-P - February 2012 13
PowerFlex DC Drive Frame B Pulse Transformer Circuit Board
Pulse Transformer Board FIR2-XX Rev. “M” and Lower
1. Refer to Tab le 1 - or Tabl e 2 - in the Sizing Resistor Configuration section
below for the appropriate configuration. Once you have determined the
correct configuration for your drive size, cut and remove the appropriate
sizing resistor(s) (if necessary) from the Pulse Transformer board.
Sizing Resistor Configuration
The tables below indicate the value of the designated resistor (R1…R5) when left
in place on the Pulse Transformer board, or “Remove” when the resistor should
be cut off and removed from the board. “–” indicates that there is no resistor in
this position on the Pulse Transformer board.
Table 1 - 230V AC Input Drives
Table 2 - 460V AC Input Drives
IMPORTANT
This procedure requires a multimeter that measures resistance to thousandths
of an ohm.
Drive Current
Rating Code
DC Amps AC Line
Amps
HP R1 R2 R3 R4 R5
146 146 119 40 – Remove Remove 5.36Ω Remove
180 180 147 50 – Remove Remove 5.36Ω Remove
218 218 178 60 – Remove Remove 5.36Ω Remove
265 265 217 75 – Remove Remove 5.36Ω 5.36Ω
360 360 294 100 – Remove 5.36Ω 5.36Ω 5.36Ω
434 434 355 125 – Remove 5.36Ω 5.36Ω 5.36Ω
Drive Current
Rating Code
DC Amps AC Line
Amps
HP R1 R2 R3 R4 R5
167 167 136.4 100 – Remove 5.36Ω Remove Remove
207 207 169.1 125 – Remove Remove 5.36Ω Remove
250 250 204.3 150 – Remove Remove 5.36Ω 5.36Ω
330 330 269.6 200 – Remove 5.36Ω 5.36Ω 5.36Ω
412 412 336.6 250 – Remove 5.36Ω 5.36Ω 5.36Ω
XP
1
X3
1
XSW
16
1
2
33
34
XR
TR2 TR1
XY
1
0V1
T04T01
T05T02
T06T03
T1
T4
T2 T5
T3 T6
K
G
KG04
K
G
KG01
K
G
KG05
K
G
KG02
K
G
KG06
K
G
KG03
K
G
KG4
K
G
KG1
K
G
KG5
K
G
KG2
K
G
KG6
K
G
KG3
XTA
1
1
78 79 35 367576U2V2
UCVW
TA
1
X4
1
F2
F3
F1
Sizing resistors are located near the center of the Pulse
Transformer circuit board.
Comentarios a estos manuales