Rockwell Automation Publication 20P-IN009D-EN-P - February 2012 17
PowerFlex DC Drive Frame B Pulse Transformer Circuit Board
Table 7 - 575V AC Input Drives
Step 5: Install the New
Pulse Transformer
Board and Existing
Switching Power
Supply Board
1. Install the new Pulse Transformer board and existing Switching Power
Supply board in reverse order of removal.
2. Replace the cables connected to connector X3, X4, XP and XR on the
Pulse Transformer board and the gate lead cables with the new cables
provided.
3. Verify that the four plastic board stabilizers mounted on the top air flow
plate are placed one on either side of each of the Pulse Transformer and
Switching Power Supply boards.
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
HP DIP Switch S3 DIP Switch S4
S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 S3-7 S3-8 S4-1 S4-2 S4-3 S4-4 S4-5 S4-6 S4-7 S4-8
67 67 55.1 50 ON ON ON ON
101 101 82.7 75 ON ON ON ON
135 135 110.3 100 ON ON ON ON
270 270 220.6 200 ON ON ON ON
405 405 330.9 300 ON ON ON ON
ATTENTION: Each gate lead cable must be connected to the exact connector
from which it was removed on the Pulse Transformer circuit board or damage to
the drive may occur.
One plastic stabilizer should be on either side of each boardAir flow plate
Plastic
stabilizers
Top view of Pulse Transformer boardSide cut-away view
Pulse Transformer board
Switching Power Supply board
Comentarios a estos manuales