Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013 47
Configuring the I/O Chapter 4
The “Use Unicast Connection over EtherNet/IP” box is checked by
default. This is the recommended setting. When this box is unchecked, the
adapter will send multicast messages on the I/O connection. In this case,
the adapter and the EtherNet/IP bridge must be on the same subnet.
9. Click OK on the New Module window.
The new node (“PowerFlex 525-E2P PowerFlex_52X_Drive” in this
example) now appears under the icon in the I/O Configuration
folder. If you double-click on the Input Controller Tag (see Controller
Input Tags on page 47) and Output Controller Tag (see Controller
Output Tags on page 47), you will see that module-defined data types and
tags have been automatically created. Note that all tag names are defined
and Datalinks include the assigned drive parameter name. After you save
and download the configuration, these tags allow you to access the Input
and Output data of the drive using the controllers ladder logic.
Controller Input Tags
Controller Output Tags
Saving the I/O Configuration to the Controller
After adding the controller and drive/adapter to the I/O configuration, you must
download the configuration to the controller. You should also save the
configuration to a file on your computer.