15–18 Creating Alarms
Publication 2711-6.0
Value Triggered Alarms
This section shows an alarm setup using a Value type trigger.
Trigger values must not exceed the range of the data type selected for
the trigger tag (signed/unsigned integer, BCD).
The following setup shows 3 alarms (A,B,C) assigned to the alm_tag
trigger. The Trigger Type is Value. The Value/Bit field shows a
different trigger value (1, 2, 3) for each alarm. The value 0 is
reserved.
In the Tag Editor, the tag definition for alm_tag is:
Tag Name Data Type Tag Address Node Name
alm_tag Unsigned Integer N15:0 SLC_1
When the value 1 is entered in N15:0, Alarm C is triggered. When
the value 2 is entered in N15:0, Alarm B is triggered and when the
value 3 is entered in N15:0, Alarm A is triggered.