20–9Terminal and Communication Setup
Publication 2711-6.0
This section shows how to define runtime parameters for a
PanelView terminal and PLC or SLC that will communicate on a
Remote I/O link.
The PanelView terminal operates as a single rack on the network.
You will define parameters for these two devices:
Remote I/O PanelView Terminal
PLC or SLC (with 1747-SN Scanner) Controller
PLC Controller PanelView Terminal
RIO Port
Remote I/O Network
SLC Controller
with 1747-SN Scanner
or
The following table defines the PLC/Scanner types with options
supported by the Remote I/O PanelView terminal.
Controller/Scanner
Lowest
Rack #
Highest
Rack #
Pass-Through Support Block Transfer Support
IBM PC 6008-SI
I
BM
PC
6008-SI
VME 6008-SV
EC S 6008-S
0 7 No Yes
V E 6008-SV
DEC QBUS 6008-SQ
0
7
No
Y
es
PLC 5/11 3 3 All Series, All Revisions Yes
PLC 5/15 1 3 Series B, Revision N or later Yes
PLC 5/20 1 3 All Series, All Revisions Yes
PLC 5/25 1 7 Series A, Revision J or later Yes
PLC 5/30 1 7 Series A, Revision B or later Yes
PLC 5/40 1 17
octal
Series A, Revision E or later
Series B, Revision B or later
Yes
PLC 5/60
PLC 5/80
1 27
octal
Series A, Revision E or later
Series B, Revision B or later
Yes
SLC 1747-SN Series A 0 3 No No
SLC 1747-SN Series B 0 3 Yes Yes
Other 1771-SN Subsystem 1 7 No No
To configure Remote I/O communications:
1. Select the Setup tab from the Terminal Setup dialog.
2. Verify the terminal name entered in the Terminal Name field
The terminal name was defined when the application was created.
Defining Remote I/O
Communications