3–7Planning an Application
Publication 2711-6.0
A tag can be assigned to any file type that the PLC, SLC or
MicroLogix 1000 supports.
PLC-5 File Types
Integer
F
Ty
R
d
d
F
N
b
E
g
Sub-Element
B
N
b
Output Read O 0
0-277➀
NA
0-17➀
Input
Read➁
I 1
0-277➀
NA
0-17➀
Status Read / Write S 2 0-127 NA 0-15
Bit (Binary) Read / Write B 3-999 0-999 NA 0-15999
Timer Read / Write T 3-999 0-999 PRE, ACC EN, TT, DN
Counter Read / Write C 3-999 0-999 PRE, ACC
CU, CD, DN.
OV, UN
Control Read / Write R 3-999 0-999 LEN, POS
EN, EU,
DN, EM, ER,
UL, IN, FD
Integer Read / Write N 3-999 0-999 NA 0-15
BCD Read / Write D 3-999 0-999 NA 0-15
Float Read / Write F 3-999 0-999 NA 0-31
ASCII Read / Write A 3-999 0-999 NA NA
String Read / Write ST 3-999 0-999 LEN NA
➀ Octal format, all other values are decimal.
➁ Remote I/O allows the PanelView to write its own output words.
➂ ControlNet terminals do not support the reading/writing of input/output tags.
SLC File Types
A tag can be assigned to any file type the SLC controller supports,
except M0 and M1.
g
F
Ty
R
d
d
F
N
b
E
g
Sub-Element
B
N
b
Output Read O 0 1-31 0-255 0-15
Input Read I 1 1-31 0-255 0-15
Status Read / Write S 2
➀
NA 0-15
Bit (Binary) Read / Write B 3, 9-255 0-255 NA 0-4095
Timer Read / Write T 4, 9-255 0-255
PRE,ACC,
1, 2
13-15, EN, TT,
DN
Counter Read / Write C 5, 9-255 0-255
PRE, ACC,
1, 2
11-15, CU, CD,
DN, OV, UN
Control Read / Write R 6, 9-255 0-255
LEN, POS,
1, 2
8-15, EN, EU,
DN, EM, ER,
UL, IN, FD
Integer Read / Write N 7, 9-255 0-255 NA 0-15
Float Read / Write F 8-255 0-255 NA NA
ASCII Read / Write A 9-255 0-255 NA 0-15
String Read / Write ST 9-255 0-255 LEN, 0-41 0-15
➀ Number of Status File elements depends on controller (e.g., SLC 5/03 has 0-99 and SLC 5/04 has 0-163).
D
F