Rockwell-automation 281E ArmorStart EtherNet/IP - Getting Started Manual de usuario Pagina 13

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 12
Publication 280E-QS001B-EN-P – February 2011
ArmorStart EtherNet/IP Distributed Motor Controller Getting Started 13
ArmorStart Receptacle Pin
Outs
Figure 13 – Receptacle Connections for EtherNet/IP (M12)
Figure 14 – Receptacle Connections for Input (M12)
Figure 15 – Receptacle Connections for Output, EtherNet/IP Version (M12)
Figure 16 – Receptacle Connections for Dynamic Brake (M22) – Bulletin 284E only
Pin 1: Tx+
Pin 2: Rx+
Pin 3: Tx–
Pin 4: Rx–
Pin 1: +24V (A3 or DNET)
Pin 2: Input 0
Pin 3: Common
Pin 4: Input 1
Pin 5: NC (no connection)
Pin 1: NC (no connection)
Pin 2: NC (no connection)
Pin 3: Common
Pin 4: Output +24V DC (A1)
Pin 5: NC (no connection)
Pin 1: GND (green/yellow)
Pin 2: BR+ (black)
Pin 3: BR- (white)
Vista de pagina 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 43 44

Comentarios a estos manuales

Sin comentarios