Publication 20D-UM002C-EN-P - November 2003
4-16 Placing and Configuring Local I/O
Using aliases to simplify tag names
An alias lets you create a tag that represents another tag. This is useful for
defining descriptive tag names for I/O values. For example:
Monitoring I/O Modules
The DriveLogix controller offers different levels at which you can monitor
I/O modules. You can:
configure an I/O module so that the controller faults if that I/O
module loses its connection with the controller
use the programming software to display fault data
program logic to monitor fault data so you can take appropriate action
Configuring the module’s response to a connection failure
You can configure modules to generate a major fault in the controller if they
lose their connection with the controller.
If you do not configure the major fault to occur, you should monitor the
module status. If a module loses its connection to the controller:
outputs go to their configured faulted state
Example: Description:
I/O structure Local:0:O.Data.0
Local:0:I.Fault.0
The aliases describe the specific I/O points.
alias light_on = Local:0:O.Data.0
light_off = Local:0:I.Fault.0