Rockwell-automation 5720 DriveLogix System Manual de usuario Pagina 235

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 263
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 234
Publication 20D-UM002C-EN-P - November 2003
DriveLogix Back-Up on DeviceNet 12-11
Table 11.1 describes the possible values this message may return when reading
the back-up state of the DeviceNet scanner.
Table 11.1
If the message reads
this value:
the back-up state of the DeviceNet scanner is:
0 Disabled
1 Primary scanner
2 Back-up scanner
3 Invalid primary node address (e.g. the node address cannot
be 62 or 63)
4 Faulted back-up scanner - CRC failure (e.g. the scanlists in
the scanners do not match)
5 Faulted back-up scanner - back-up node number failure (e.g.
the back-up scanner is not using a node number = the
primary node number + 1)
6 Back-up scanner pending primary detection
254 Attempting primary access
255 Attempting back-up access
Vista de pagina 234
1 2 ... 230 231 232 233 234 235 236 237 238 239 240 ... 262 263

Comentarios a estos manuales

Sin comentarios