Rockwell-automation 6012DB PowerFlex Medium Voltage Variable Frequency Manual de usuario Pagina 111

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 138
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 110
Rockwell Automation Publication 6000-UM001B-EN-P - October 2014 111
Preventative Maintenance and Component Replacement Chapter 5
5. Refer to the Electrical Drawings for reconnecting the fiber optic wires.
Inspect the HMI
1. Verify the input and output cables and communication cables are hand-
tight.
2. Power up the HMI.
3. Verify the HMI display is operating normally.
Replace the HMI
The touch screen is located on the LV Control Cabinet door.
Connect Fiber Optic Wires here
(Refer to Electrical Drawings)
Reconnect the HMI
Communication Cable
Reconnect the bottom terminal
ATTENTION: Always perform Power Lockout procedure before servicing
equipment. Verify with a hot stick or appropriate voltage measuring device that
all circuits are voltage free. Failure to do so may result in severe burns, injury, or
death.
Vista de pagina 110
1 2 ... 106 107 108 109 110 111 112 113 114 115 116 ... 137 138

Comentarios a estos manuales

Sin comentarios