Rockwell-automation 6012DB PowerFlex Medium Voltage Variable Frequency Manual de usuario Pagina 27

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 138
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 26
Rockwell Automation Publication 6000-UM001B-EN-P - October 2014 27
Drive System Layout Chapter 2
The status information of the Power Module is transmitted through the
electrical-optical converter and sent to the main control unit. When there is a
fault, the main control unit sends control signals to lockout or bypass the affected
Power Module.
The Power Module cabinet consists of Power Modules, current transformers and
high-voltage cable.
The Power Modules are divided evenly into three phases (U, V, and W). The
units in each phase are connected end-to-end at the output terminals. Then
individual phases are formed, using a star connection. Current transformers are
installed into the U phase and W phase.
Different models of Power Modules are used for VFDs of different power ratings
(Figure 19
).
Figure 19 - Typical Fixed-mounted Power Module
Line Terminals
Fuse
Optic Fiber Socket
and Status Indicator
Output Terminal
Vista de pagina 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 137 138

Comentarios a estos manuales

Sin comentarios