Chapter 4 Drive Terminal Application
Alarms
In the PowerFlex 7000, “Alarms” refer collectively to ‘Faults’ and ‘Warnings’. The
Alarms screen, typical of Figure 36
, provides two tabs to independently show the
Wa rn i n g s o r th e Fau l t s .
Figure 36 - Alarm Screen
Select the desired queue by selecting the tab. The operation of both queues is
identical.
The queue contains three columns:
The name of the alarm,
A code associated with the alarm
Timestamp
TIP
The Alarm Screen Common Panel shows a timestamp for the last time the drive
was started and stopped for any reason.