Rockwell-automation 7000 PowerFlex HMI Offering with Enhanced Function Manual de usuario Pagina 63

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 90
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 62
Rockwell Automation Publication 7000-UM201B-EN-P - June 2013 61
Drive Terminal Application Chapter 4
Place the Drive into Download Mode
To load new firmware or other modules to the PowerFlex 7000 drive, it must first
be placed into download mode. A minimum of “Advanced” access level is
required to perform this operation.
1. Press Download (Figure 57
).
Figure 59 - Download Confirmation
2. Press OK to confirm the task.
If the operation cannot be completed, the dialog in Figure 60
is displayed
and the action will be aborted.
Figure 60 - Download Request Failed
If the request is successful, the message in Figure 61, is displayed and the
terminal application closes.
Figure 61 - Download Request Successful
Vista de pagina 62
1 2 ... 58 59 60 61 62 63 64 65 66 67 68 ... 89 90

Comentarios a estos manuales

Sin comentarios